A cable is only as good as its ends. Termination is the work of finishing a cable end so that it connects to a breaker, a busbar, a motor, a socket or a piece of equipment: the conductor is stripped, fitted with a lug or a connector, tightened and, on armoured cable, clamped in a gland. Jointing is the work of joining two lengths of cable into one, and repair is the work of making a damaged cable safe again. These three are the places where a cable's factory-made insulation and sheath are removed and rebuilt by hand, so a cable is weakest there when the work is poor.

Circuit Dubai terminates, joints and repairs low-voltage cable in villas, apartments, offices, shops, warehouses and plant rooms across Dubai. We fit crimp lugs and connectors, armoured cable glands and EMC glands, straight joints and repair sleeves, and we test the result before we leave. We are electricians first, so the termination, the connection to the board or the machine, and the test are one job with one person responsible.

Hand crimping a fork terminal onto a wire with a crimping tool beside a terminal block, cable termination and crimping in Dubai

What cable termination and jointing with us includes

A look at the cable first, covering its type, size, number of cores, armour, voltage and the condition of the insulation and sheath.

The right termination for the cable and the equipment, with a lug or connector sized to the conductor, a gland sized to the cable, and the right tool for each.

Joints and repairs that restore every layer, meaning the conductor, the insulation, the armour or screen, and the outer sheath.

Clean, labelled work, with phases and polarity marked, torque marks on the bolts and no loose strands.

Tests before we leave, with insulation resistance, continuity of the armour and, on three-phase cable, the phase order.

Honest advice on repair or replace, since a new length of cable suits a short run and a joint suits a long buried run.

The numbers at a glance

Typical answer for Dubai

What we terminateCrimp lugs and connectors, ferrules, armoured and EMC cable glands, heavy cable lugs, busbar and breaker connections
What we joint and repairLow-voltage straight joints, sheath repairs, damaged power cable, damaged flexible cable
PropertiesVillas, apartments, offices, shops, warehouses, workshops and plant rooms
VoltageLow voltage, 230 V and 400 V. 11 kV and 33 kV work is explained in its own section
What we need to quotePhotos of the cable and the damage, the cable label or printing, the size and the number of cores
VisitA short look at the cable and the equipment before any quote. The visit costs AED 50.
ResultA finished, labelled and tested termination or joint, with the test figures written down
PriceQuoted per termination, per joint or per repair

Before you book termination or jointing work, photograph the cable end or the damaged part, and photograph the printing on the cable sheath, which gives the maker, the voltage and the size. Count the cores, note whether the cable has armour or a metal screen, and say what it connects to and whether it is indoors, outdoors or underground. If a cable is damaged, say how it was damaged and whether the supply is off. That is enough for us to say whether a new termination, a joint or a new length of cable is the right answer and to give a first price. The sections below explain the choices so you can judge any quote before you accept it.

Terms

Cable termination and jointing terms: what people search for and what each means

People search for this work by the part in their hand or by the problem in front of them. The tables below match the wording to what is involved, and the later sections give the detail. Some of the terms belong to high-voltage utility work, and the table says so where that is the case.

Crimp connector and termination terms

If you searchedWhat it means
Termination in electrical wiring, termination connectorsThe way a conductor is finished and connected to something. The connector can be a crimp lug, a ferrule, a screw terminal or a gland, depending on the cable. See the termination sections
Wire termination connectors, cable termination connectorsThe lug, ferrule or sleeve fixed to the end of a conductor so it can be connected. See the crimp connector section
Crimp termination connectors, crimp type wire connectors, crimp on wire connectors, wire crimp on connectorsConnectors fixed to the wire by squeezing the metal barrel onto the conductor with a crimp tool. See the crimp connector section
Cable crimp connectors, electrical cable crimp connectors, electrical wire crimp connectorsThe same family, sold by cable or wire size. The size matters more than the name. See the crimp sizes part of the crimp connector section
Wire to wire crimp connectorsA butt connector, a parallel connector or a bullet pair that joins one wire to another. See the crimp connector section
Brass wire crimp connectorsA connector with a brass barrel. See the brass and copper part of the crimp connector section
Yellow crimp connectorsThe colour of the largest size in the red, blue and yellow insulated range. See the colours and sizes part
Speaker crimp connectors, speaker wire crimp connectors, audio crimp connectorsSmall connectors for speaker and audio cable, such as spade, pin and banana plugs. See the speaker and audio section

Gland, joint, repair and kit terms

If you searchedWhat it means
Armoured cable gland installation, fitting armoured cable gland, armoured cable gland fitting instructionsThe fitting that grips the armour of an armoured cable where it enters a board or a box. See the armoured cable gland section
Connectwell cable glandConnectwell is a make of cable gland. We fit the make the job specifies, and we do not claim to be an authorised dealer. See the armoured cable gland section
EMC cable gland installationA gland that connects the metal screen of a cable all the way round to the enclosure. See the EMC gland section
Power cable repair, electrical cable repairMaking a damaged power cable safe, by a repair sleeve, a joint or a new length. See the repair section
Wire cable repair near meOur office is in Al Quoz and we work across Dubai. See the repair section and the why-us section
EV charging cable repairA damaged charging cable is replaced and not spliced. See the EV charging cable section
Cable joint kit price, cable jointer price, termination kit price, cable termination kit price, cable jointing companiesWhat a kit or a jointer costs depends on the voltage, the size and the type of joint. See the cost section
11kV termination kit price, 11kV end termination kit price, 11kV cable joint kit price, 11kV XLPE cable jointing kit priceMedium-voltage cable accessories for utility and high-voltage work. See the 11 kV and 33 kV section
33kV termination kit price, 33kV end termination kit price, 33kV cable termination kit price, 33kV cable jointing kit priceThe same kind of accessory for 33 kV cable. See the 11 kV and 33 kV section
Choosing

Termination, joint or repair: choosing the right answer

A termination finishes a cable end. A joint joins two cable ends into one. A repair restores a cable that was damaged. The three look alike because they use the same tools and kits, but they solve different problems, and a wrong choice costs money. The first choice is whether a joint is needed at all.

SituationBest answerWhy
A new cable to a board, a machine or a pumpTermination with a lug and a glandThe cable ends there, and a good termination is the whole job
A cable that is a few metres too shortA new full length where it can be reachedOne continuous cable has no joint that can fail
A long buried or concealed cable, cut by a drill or a diggerA straight joint at the cutReplacing the whole length means digging the whole route again
A nick in the outer sheath with the conductors untouchedA sheath repair sleeve or wrapThe cable is sound inside, and the sheath is the water barrier
A burnt or melted terminationA new lug and a cut-back, after finding why it overheatedA burnt lug points to a loose bolt, a wrong lug size or an overload
A damaged flexible cord or extension leadReplace itA cord is a made and tested product, and a repaired one is a weak point
A damaged EV charging cableReplace the cable assemblySee the EV charging cable section
A cable that has to change direction or reach a new placeA new route with a termination at each endA joint is a fix, and a new route is a design

The table shows the rule we work to: use one length of cable where we can and a joint only where we must. A joint is a tested, skilled piece of work, but it is also the one place on the cable where the maker's insulation has been replaced by a kit and a pair of hands.

Rules

Rules and standards for cable termination and jointing in Dubai

Cable termination and jointing sit under the wiring regulations, the cable maker's instructions, the kit maker's instructions and, for a utility cable, the supply authority's rules. We are electricians and not lawyers, so confirm what applies to your building with the building management, your consultant or the authority.

What applies and where it comes from

SubjectWhat applies
Wiring regulationsDEWA publishes Regulations for Electrical Installations, and the 2017 edition is listed on its website. This page does not repeat DEWA's clause numbers. Where we give a figure, it comes from an international standard or a maker's guide, and we check the DEWA requirement for your building before work starts.
Joints and connectionsBS 7671, the UK wiring standard, says every connection must be accessible for inspection, testing and maintenance, with listed exceptions. The exceptions include joints in the ground, compound-filled or encapsulated joints, and properly compression-made joints. A termination inside a board or a box is accessible by design.
Crimped connectionsIEC 60352-2 is the international standard for solderless crimped connections, and it sets how a crimp is made and tested. Terminal makers publish the tool, the die and the wire range for each terminal, and the crimp has to follow them.
Cable glandsThe gland maker's instruction sheet sets the sheath strip length, the armour clamping and the tightening. Glands for hazardous areas are certified products, and a certified gland has to be fitted exactly as its certificate says.
Joint and termination kitsEach kit comes with a maker's installation sheet with dimensions, cleaning steps and heating or shrinking steps. The sheet is the method, and a jointer works to it
Utility and medium-voltage cableDEWA keeps its own requirements for jointers and for contractors who lay 11 kV, 33 kV and low-voltage cable for the network. Ask the supply authority before any work on a utility cable.
PermitsA hot-work permit can apply where a gas torch is used for heat-shrink work inside a building. Cold-shrink and resin joints avoid the flame.

Why the maker's sheet decides the method

Every kit and every gland has dimensions that matter to the millimetre: how much sheath to remove, how far the armour is cut back, how much insulation is stripped from the conductor and how long a heat-shrink tube must be shrunk. One maker's instruction sheet for a gland, for example, says to remove a further 18 mm maximum of outer sheath to expose the armour, and gives no tightening torque. A different gland needs a different length. A termination made from memory instead of from the sheet is how a gland or joint fault begins. We keep the sheet with the kit and work through it, and we write down anything the sheet leaves to the installer, such as the torque of a bolt, from the bolt maker's table.

Why an accessible joint matters

A joint buried in plaster cannot be inspected, and a joint that heats inside a wall fails unseen. So where a connection is not a sealed, compression-made joint in the ground, we make it in a box or an enclosure that opens, and we show the position on the drawing. A crimped butt connector inside a junction box is an accessible connection. A crimped butt connector taped and plastered into a wall is a hidden one. See our conduit, trunking and cable tray page for the junction box rules, which apply here as well.

Crimp connectors

Crimp connectors: wire termination connectors, wire to wire crimp connectors, sizes and a good crimp

A crimp connector is a metal sleeve or lug that is squeezed onto the end of a conductor with a crimp tool. The squeeze compacts the strands and the metal barrel into one solid mass with no air between them, and that mass carries current and resists a pull. Crimping is the way wire termination connectors and cable termination connectors are fixed in switchgear, control panels, motors, vehicles, speakers and plant, because a correct crimp is quick, repeatable and tested by standard. A crimp is only as good as the match between the wire, the connector and the tool.

Which connector for which wire

ConnectorWhat it doesWhere we use it
Ring terminalA closed loop that goes round a stud or under a screw and cannot slip offBolted connections on boards, motors, earth studs and battery posts
Fork or spade terminalAn open U that slides under a screw head without removing the screwTerminal blocks and screws where the screw cannot be taken out
Pin terminal and ferruleA solid pin or tube that gathers the strands of a flexible wire into one neat endStranded wire going into a screw or clamp terminal
Push-on blade and receptacleA flat tab and a socket that push togetherAppliance and control connections that have to be unplugged
Butt connectorA tube, crimped from both ends, that joins one wire to another in a lineWire to wire crimp connectors in a junction box
Parallel or end-to-end connectorA tube that takes two or more wires entering from the same sideJoining several wires in a box with little space
Bullet connectorA male and a female pair, crimped one on each wireA joint that has to be separated again, such as a light or a fan lead
Heat-shrink butt connectorA butt connector with a heat-shrink sleeve and a sealant insideWet places and outdoor wire to wire joints

Insulated versions have a plastic sleeve that covers the barrel. Non-insulated versions are bare and are covered afterwards with a heat-shrink boot or a sleeve. A crimp on wire connector for a house circuit should be insulated or sleeved, and it should sit inside a box.

Crimp colours and sizes

Pre-insulated terminals are colour-coded by the size of wire they take, so an installer can pick the right one without reading the packet. Maker charts for pre-insulated terminals pair red with about 0.5 to 1.5 mm², blue with 1.5 to 2.5 mm² and yellow with 4 to 6 mm². That makes yellow crimp connectors the largest of the three. A ratchet crimp tool listed in a trade catalogue for red, blue and yellow terminals covers 0.5 to 6 mm² overall, which fits that pairing.

Two cautions apply. A colour stands for a range of wire sizes and not a single one, so a wire at the thin end of a range needs a good crimp with the right die and not a lighter squeeze. And a colour on a bootlace ferrule does not mean what the same colour means on a ring or a fork terminal, because ferrule colours differ between makers and standards. We read the printed size and the maker's chart. We do not rely on the colour alone.

Brass, copper and tin plating

The barrel of a crimp connector is copper, tinned copper or brass. Brass wire crimp connectors are made from a harder metal than copper and are used for pins, plugs and bullets. Copper conducts better than brass, and tin plating protects copper from corroding. For a power connection we choose by the connector's printed current rating and its wire range, and the metal's name matters less than the rating.

Making a good crimp

A good crimp is made in the same few steps every time.

1

Strip to the length the terminal needs. The conductor should show at the end of the barrel and should not reach the insulating sleeve. Cut or nicked strands weaken the crimp, so we use a stripper set to the wire.

2

Twist loose strands into one bundle before they enter the barrel, and push the conductor right in.

3

Use the right die nest. A ratchet crimp tool has marked or colour-coded nests for the red, blue and yellow sizes, and the terminal sits in the nest that matches it. A ratchet tool cannot be opened until the crimp is complete, which stops a half-made crimp from passing as a finished one.

4

Close the tool fully. The barrel is crimped over the conductor and, on an insulated terminal, a second crimp holds the plastic sleeve on the insulation.

5

Tug it. A hand pull on the wire and a look at the crimp show a loose one at once. Terminal makers also test crimps in a laboratory, and a good crimp cut open shows the strands compressed evenly, in a honeycomb pattern with no gaps. A quality crimp resists a pull-off force that is checked in newtons and compared with the force that breaks the wire itself.

We do not squeeze a terminal with ordinary pliers. An ordinary plier can flatten one side of the barrel and leave the strands loose inside it, and the connection looks right and then heats under load.

Crimp, screw terminal or solder

A crimp is the right termination for a lug on a power cable, for a ferrule on a flexible wire and for a wire to wire joint in a box. A screw terminal takes a ferruled or solid conductor directly, and a bare stranded wire under a screw spreads out and loosens as it settles, so we ferrule it. Our practice is not to solder lugs on power cables, because solder can creep under the pressure of a screw and it stiffens the wire where it meets the lug, which is where a flexed wire breaks.

Heavy cable

Heavy cable terminations: lugs, busbars and termination in electrical wiring

Termination in electrical wiring is the point where a cable stops being a cable and becomes a connection. On small wire the termination is a ferrule under a screw. On heavy cable, such as the incoming cable to a distribution board, a generator or a motor control panel, it is a compression lug on each conductor, bolted to a busbar or a breaker, and a gland where the cable enters the enclosure. The same rules apply as for a crimp connector, with bigger tools and more consequence if the work is wrong.

The steps of a heavy cable termination

  1. 1
    Cut the cable to length with a margin, and support it so its weight does not hang on the lugs.
  2. 2
    Remove the outer sheath and fit the gland on armoured cable. See the armoured cable gland section for the gland steps.
  3. 3
    Separate the cores and strip the insulation to the depth of the lug barrel. A lug with an inspection hole in the barrel shows that the conductor has reached the end.
  4. 4
    Fit the lug and crimp it with a hydraulic or mechanical tool and the die made for that lug and conductor size. The lug maker's sheet gives the number of crimps and the die.
  5. 5
    Cover the barrel with a heat-shrink boot or a tape wrap in the colour of the phase, and mark each core at both ends.
  6. 6
    Bolt the lug to its busbar or breaker with the bolt, washers and nut the equipment maker specifies, and tighten to the torque from the maker's table. We mark the bolt head with a line of paint across the nut and the washer, so a loosened bolt can be seen on the next inspection.
  7. 7
    Check the clearances, since bare metal on one phase must be clear of the next phase and of the enclosure.

Matching the lug to the conductor and the stud

A lug has two sizes: the barrel size for the conductor cross-section and the hole size for the stud or bolt. A lug with the right barrel and a hole that is too big sits loose on the bolt and heats. A lug with the right hole and a barrel that is too big grips the conductor badly. We check both before the crimp.

Copper and aluminium conductors are not interchangeable in a lug. Aluminium conductors need lugs made for aluminium, or bimetallic lugs where the busbar is copper, and the maker's instruction on oxide-inhibiting compound has to be followed, because aluminium forms an oxide skin that raises the resistance of the joint.

Mechanical connectors and shear bolts

Some connectors do not use a crimp tool. A mechanical connector has bolts that clamp the conductor, and in a shear-bolt connector each bolt head is made to break off at the right torque, which makes the tightening independent of the installer's arm. One kit's instruction sheet tells the installer to tighten the bolts in sequence until the shear heads break, to file off sharp edges and to fill the bolt holes with semi-conducting tape. We follow the sheet of the connector in the box, because a kit with shear bolts and a kit with hex crimps are different jobs.

Heat and Dubai

A termination that is loose or undersized heats under load, and a hot plant room or a roof in a Dubai summer leaves less margin for a loose connection. A termination in a hot place is checked more closely and is worth a thermal inspection after a few weeks of load. See our thermal imaging inspection page for how a camera finds a hot lug before it fails.

Speaker and audio

Speaker and audio crimp connectors

Speaker crimp connectors are small terminals for the end of speaker wire: spade, pin, ring and banana plugs, in crimp form or screw form. They are neater than bare wire in a binding post, and they stop strands from touching the next terminal. A strand of speaker wire that touches the wrong post can short the output of an amplifier.

Speaker wire crimp connectors are sized to the wire gauge. A 16 AWG speaker wire has a cross-section of about 1.3 mm², 14 AWG about 2.1 mm² and 12 AWG about 3.3 mm², so the terminals that suit 16 and 14 AWG sit within the red and blue range described above, and 12 AWG needs a larger one. We match the terminal to the printed wire size and not to the speaker brand.

Audio crimp connectors for line-level signals, such as RCA and XLR plugs, depend on the plug. Some are soldered, some use screw terminals and some use a crimp, and the plug maker's sheet says which. For all audio connectors:

  • keep the polarity: the marked wire, such as the ribbed or striped one, goes to the same terminal at both ends;
  • strip only what the barrel takes, so no loose strand reaches the next pin;
  • tug each crimp and check there is no stray strand before the plug is closed.

For gauge, length and layout of a speaker system, see our home cinema and audio wiring page.

Armoured glands

Armoured cable gland installation: fitting instructions, BW and CW glands, sizing and earthing

An armoured cable gland is the fitting that holds an armoured cable where it enters a distribution board, a control panel, a junction box or a machine. Steel wire armoured cable, called SWA, has copper conductors, insulation, a bedding layer, a layer of steel wires and an outer sheath. The gland has three jobs: it holds the cable so a pull on the cable does not reach the conductors, it clamps the armour wires so the armour is bonded to the gland and to the enclosure, and, on an outdoor type, it seals the entry against water. A gland that does one of the three badly is a fault waiting for the first wet day or the first tug.

How an armoured cable gland grips the armour

A standard brass gland is made of two main parts. A cone sits inside the entry, and a nut and a clamping ring tighten onto it. The armour wires are spread around the cone, and the ring squeezes them against it when the nut is tightened, so the armour is both held and electrically bonded to the metal body. A locknut fixes the gland to the enclosure wall. An earth tag, a washer with a tail, sits under the locknut so the armour can be wired to the earth bar of the board. A shroud, made of PVC or low smoke zero halogen material, covers the metal for protection and a neat finish. A gland kit is sold as a gland with a locknut, an earth tag and a shroud, and a cable has two ends, so a cable needs two kits.

Choosing BW or CW

The two main types answer one question: does the outer sheath need a seal?

TypeSeals the outer sheathWhere we use it
BWNo. It grips the armour onlyDry, indoor terminations in a board or a panel inside a building
CWYes. A compression seal tightens onto the outer sheathOutdoor, wet, dusty or washdown places, or where the entry has to carry an IP rating

A gland supplier's guide gives IP66 or better as the rating of a CW outdoor gland, and the rating holds only when the gland is the right size for the cable and is tightened as the sheet says. In a Dubai pump room, a roof plant area, a car park or a garden panel, where hot weather, cleaning water and dust meet, we use the sealed type. Inside a dry electrical room, a BW gland is the correct fit. A BW gland on an outdoor cable has no seal at the sheath and lets water run down the cable into the board.

Sizing a gland

A gland is chosen by the cable and by the hole, and a wrong size is the first thing to check. The cable side is set by the overall diameter of the cable, the thickness of the armour wires and the number of cores. The hole side is set by the thread, such as M20, M25 or M32, which has to match the entry in the enclosure. A maker's chart lists each gland size against cable size. As an example, one UK supplier's chart lists a BW20S or CW20S gland for two-core cable of 1.5 to 6 mm². The chart is a guide, and the gland maker's own table decides.

An undersized gland cannot take the cable. An oversized gland cannot grip the armour or squeeze the seal, and the armour can pull out when the cable is tugged. We measure the cable at the point the gland will sit, not the figure on a drawing.

Fitting an armoured cable gland step by step

These are the steps for fitting an armoured cable gland, and the instruction sheet of the gland in the box decides every dimension.

  1. 1
    Confirm the cable and choose the gland. Check that it is armoured cable, pick BW or CW for the place, and pick the size from the maker's chart.
  2. 2
    Slide the shroud onto the cable first. It cannot be fitted after the gland is tightened.
  3. 3
    Prepare the cable. Strip the outer sheath to suit the equipment, then remove a further length of outer sheath to expose the armour. One maker's sheet for its BW gland gives this length as 18 mm maximum. Another gland needs another length.
  4. 4
    Fit the gland entry into the enclosure, with the locknut, and the earth tag under the locknut where the enclosure is metal. Where the hole is not threaded, the locknut holds the gland.
  5. 5
    Pass the cable through and spread the armour wires evenly round the cone, with none crossed or missing.
  6. 6
    Tighten the nut. Push the cable forward so the armour stays on the cone, tighten the nut by hand, then hold the entry with a spanner and tighten the nut with a second spanner until the armour is secured. One maker's sheet gives no torque figure, so the grip is judged by the maker's instruction and a tug test.
  7. 7
    On a CW gland, tighten the seal onto the outer sheath until it is compressed all round.
  8. 8
    Connect the earth tag with a copper earth conductor to the earth bar, where the design uses the tag.
  9. 9
    Slide the shroud over the gland.
  10. 10
    Inspect. The seal is compressed, the armour is held evenly, no strands stand out, and the cable does not move when pulled.

A plastic enclosure does not carry the armour to earth the way a metal one does, so the earth tag and its conductor matter more there. A painted metal enclosure needs the paint removed where the gland or the earth tag touches, or the paint insulates the contact.

Whether the armour is the earth

Armour can carry earth fault current only where the designer has sized it for that, and armour has a higher resistance than a copper conductor of the same cross-section. Some designs rely on the armour as the protective conductor, and others add a separate earth core or a copper earth. We follow the design and the cable data, and we test the continuity afterwards. See our earthing and grounding page for how earth paths are tested.

Connectwell cable gland and other makes

Connectwell is a make of cable gland. We fit the make that the job specifies, or an equal of the same type and rating, and we do not claim to be an authorised dealer or distributor of any make. A gland from one maker and a locknut or a shroud from another can fit badly, so we use the parts from one kit.

Hazardous areas

A gland for a place with flammable gas or dust is a certified product, and the certificate sets how it is fitted. We do not fit a certified gland from a general instruction.

Faults we find at glands

  • A BW gland on an outdoor cable, with water running into the board.
  • A gland too big for the cable, so the armour was never gripped.
  • An armour wire cut short or left outside the cone.
  • A missing shroud, so bare metal and sharp wire ends are exposed.
  • No earth tag connection in a plastic board.
  • A nut over-tightened until the sheath is cut.
  • A gland fitted to a cable that is not armoured, so it grips only the sheath.
EMC glands

EMC cable gland installation: connecting a cable screen all the way round

An EMC gland connects the metal screen of a cable to the enclosure all the way round, so that electrical noise stays inside the cable and does not leak out or leak in. EMC stands for electromagnetic compatibility. The glands are used where a variable-speed drive feeds a motor through a screened cable, where control and data cables run beside power cables, and where instruments are sensitive to noise. A drive on a pump, a fan, a lift or a chiller sends sharp-edged pulses down the motor cable, and the screen and its gland are what keep those pulses out of the other wiring.

What an EMC gland does differently

A standard gland holds the cable and seals it. An EMC gland also makes a low-resistance metal contact with the braid or foil screen around the full circumference, which is called a 360 degree connection. A nylon gland insulates the screen from the enclosure. A single-seal brass gland touches the braid at one point only, and that one point is a weak path for noise. An EMC gland has an internal cone or spring and an external nut, in stainless steel or nickel-plated brass, that clamp the screen all the way round.

EMC gland installation steps

  1. 1
    Strip the outer jacket without disturbing the braid. Use a tool that does not cut the strands.
  2. 2
    Push the braid back into a cylinder so it forms an even ring.
  3. 3
    Fold any drain wire back under the ferrule or the cone, and do not leave it as a short tail.
  4. 4
    Fit the cone or ferrule over the braid and tighten the nut until the braid shows a slight embossing, which shows firm metal to metal contact.
  5. 5
    Land the screen on the protective earth bar, not on a functional or signal earth rail, so noise does not pass into the logic grounds.
  6. 6
    Keep the unscreened part of each conductor short, because the bare conductors beyond the screen act as antennas.
  7. 7
    Measure it. A milliohm meter between the screen at the far end and the earth bar of the board shows a high reading where a hidden pigtail, a loose cone or paint under the nut breaks the path.

Where an EMC installation goes wrong

ErrorWhy it mattersFix
Screen drain wire left as a pigtailA short tail acts as a small inductor at high frequency and lets noise outClamp it under the ferrule
Wrong gland typeA nylon gland insulates the screen and a single-point gland contacts it at one placeAn EMC gland with a cone and an external nut
Painted panel under the glandPaint insulates the nut at high frequencyRemove the paint under the nut and recheck the tightness after a day
Armour used as the earth returnArmour has a higher impedance than copperRun a separate copper protective conductor and bond the armour at both ends
Spare screens left floatingAn unconnected screen acts as an antennaBond every screen, spare ones at the cabinet end only
Screen on a signal earth railNoise travels into the control groundsMove the screen to the protective earth bar

An EMC gland is not needed on every cable. It is the answer to a screened cable and a noise risk, and where there is no screened cable a standard gland is the right fit. For the cable and the earthing of a motor, see our motor and lift wiring page. The drive maker's manual states the screening and gland requirements for that drive, and we follow it.

Joints and repair

Cable joints and power cable repair: the sheath, the conductor, the armour and the seal

Power cable repair is the work of making a damaged cable safe and watertight again, and it comes in different sizes. A nick in the outer sheath is one repair. A cable cut by a drill or a digger is another. A crushed, burnt or soaked cable is a third. The right fix depends on how deep the damage goes, whether the circuit can be switched off, and how long the cable is.

Stop and keep clear of a cable that is cut, crushed, burnt, hot or lying in water until the circuit is isolated at the board and tested dead. A damaged cable can still be live, and touching exposed conductors or wet armour can kill. Do not wrap a damaged cable in tape and put the supply back on. Switch off the breaker that feeds it, keep people and pets away, and call an electrician. Where the cable is outside or underground, tell us whether any work with a drill, a breaker or a digger was going on nearby.

What a joint has to restore

A cable has four layers that matter, and a joint or a repair has to restore each one.

  • The conductor. Each core is joined with a crimp ferrule or a mechanical connector sized to the conductor, and a crimp is made with the hydraulic tool and die that suit the ferrule. In a small space the connectors on each core can be staggered so the joint stays slim.
  • The insulation. The joint replaces the maker's insulation with a heat-shrink tube, a cold-shrink tube or a resin fill, and it is cleaned, shaped and sealed as the kit sheet says.
  • The armour or screen. The armour must run through the joint, or be bridged across it, so the earth path and the mechanical protection are not broken. A joint on an armoured cable that does not carry the armour across it breaks the path that the armour provided.
  • The outer sheath. The joint is sealed at the sheath so water does not run along the cable and into the joint.
Junction box with loose copper wires and hot labels, junction box with joined wires in Dubai

Choosing the repair

DamageRepairNotes
Sheath nicked, slit or torn, conductors soundRepair sleeve or wrap-around sheath repairRestores the water barrier. Wrap-around heat-shrink kits mend nicks, slits and tears without disconnecting the supply, and a cold-shrink sleeve suits a place where hot work is not allowed and the circuit can be switched off
Armour wires cut or crushed, insulation soundArmour repair with a bridge and a sheath repairThe earth path has to be restored
Insulation or conductor cut or burntStraight joint, or cut out and replaceThe damaged length is removed and the ends joined
Cable crushed or kinkedCut out the crushed part and jointA crushed cable can have inner damage that does not show
Cable soaked after flooding or a burst pipeDry, test and decideA cable that fails an insulation test is cut back or replaced
Burnt lug or melted terminationCut back to sound cable and fit a new lugFind why it overheated first

Resin, heat-shrink and cold-shrink joints

Three technologies make a low-voltage straight joint.

TypeHow it worksFlameNotes
ResinA two-part resin is mixed and poured into a shell around the joined cores, where it cures into a solid blockNoSuits armoured and multicore cable in a place where a mould can sit level. The curing time is on the kit sheet
Heat shrinkTubes shrink onto the cores and conductors when heatedYes, a gas torchThe tubes are shrunk from the centre toward the ends, and the kit sheet gives the heating method
Cold shrinkTubes are expanded on a removable core, and unwinding the core lets them shrink onto the cableNoKits exist for polymeric cable such as XLPE and EPR. No torch is needed, which suits a place where hot work is not allowed

A kit is chosen by the cable's size range and type, the place, whether a flame is allowed, and any fire or low smoke requirement. We choose with the cable data in hand, and we do not use a kit outside its size range.

The steps of a joint

A typical straight joint on a low-voltage armoured cable follows this order, and the kit sheet fixes the lengths.

  1. 1
    Isolate and prove dead, and earth the cable ends.
  2. 2
    Cut the cable ends square and remove the outer sheath, the armour and the bedding to the lengths on the sheet.
  3. 3
    Strip the insulation from each core to the depth of the connector.
  4. 4
    Crimp the connectors with the hydraulic tool and the die for the ferrule.
  5. 5
    Rebuild the insulation with the tubes or the resin fill, working cleanly and in the order the sheet gives.
  6. 6
    Bridge the armour across the joint with the earth braid or the armour clamps in the kit.
  7. 7
    Seal the outer sheath at both ends of the joint.
  8. 8
    Test before the cable is energised.

Joints in the ground and in buildings

A joint buried in the ground, or a resin joint that is encapsulated, falls within the listed exceptions to the accessible-joint rule in BS 7671. In a building, we try to avoid a joint in a wall or ceiling at all, and where one is unavoidable we mark its place on the drawing and tell you. A cable buried in the ground is traced with a cable locator before any digging, so a repair does not become a second cut.

What we do not recommend

Tape is not a repair. A joint made with a pair of connectors and electrical tape has no seal, no armour bridge and no strain relief, and it looks sound until the first wet day. A joint made without a test is a guess. We tell you when the honest answer is a new length of cable. See our insulation and earth resistance testing page for the tests we run on a repaired cable.

Repair near you

If you searched for wire cable repair near me, our office is at Office 1271, Oasis Mall, Al Quoz 1, Dubai, and we work across the areas listed on this page. Send photos of the damage, the cable printing and the place, and tell us whether the supply is off. We answer emergency messages 24 hours a day, 7 days a week, and a technician can be on site within 30 minutes anywhere in Dubai.

EV charging cable

EV charging cable repair: when to replace and what we repair

EV charging cable repair is a different question from power cable repair, because a charging cable is a made assembly. It has a plug at the car end, a plug or a fixed connection at the charger end, power conductors and signal conductors, and it is built and tested as one product. A splice in the middle of it is not a part of that design.

Charger-care guides list the signs of a failing cable: cracks or splits in the insulation, fraying or exposed wires, discolouration from overheating, bent or damaged pins, loose connections and corrosion or moisture. One such guide says to replace a cable at once when it has exposed internal conductors, overheats repeatedly, has connectors that no longer hold, or interrupts charging at random. We follow the same rule. We do not splice a damaged charging cable. We replace the cable assembly, or we direct you to the maker, because a splice puts the cable outside the maker's tested design, and the warranty terms are the maker's to state.

What we do repair is the fixed wiring around the charger:

  • the supply cable from the board to the charger, where it is damaged or burnt;
  • the gland and the termination at the charger or the board;
  • a lug or a connector that has overheated.

Switch the charger off at its breaker and unplug the cable only if it is safe to reach. Do not use a damaged cable, and do not use an extension lead as a substitute. For the charger itself, see our EV charger installation page, and for a wall unit with a damaged cable that belongs to the unit, see our Tesla Wall Connector service page.

11kV and 33kV

11kV and 33kV cable joints and terminations: what the kits are and who does the work

Some of the searches that reach this page are for medium-voltage cable accessories: an 11kV termination kit price, an 11kV end termination kit price, an 11kV cable joint kit price, an 11kV XLPE cable jointing kit price, a 33kV termination kit price, a 33kV end termination kit price, a 33kV cable termination kit price or a 33kV cable jointing kit price. They are searches for the parts, and this section says plainly what the parts are, what sets their price and who is allowed to fit them. It is not a guide to doing the work yourself, because 11 000 and 33 000 volts are lethal, and the work belongs to certified specialists.

Why medium voltage is a different trade

At a cut end of a medium-voltage cable the metal screen stops, and the electric field in the insulation bunches up where the screen ends. A termination or a joint has to spread that field out again, and that is the job of a stress control part, either a tube or a mastic wrap, that is fitted over the end of the screen. A small error in the cut, a trace of dirt or a gap in the insulation can start a discharge that eats through the insulation over time and ends in a fault. That is why medium-voltage jointing is done to a maker's sheet with dimensions in millimetres, and with cleaning steps that run in one direction only.

What is in an MV joint kit

One maker's instruction sheet for an 11 kV straight joint on three-core XLPE cable, for conductors of 25 to 630 mm², gives an idea of what a kit contains and how the work runs. The kit holds stress control tubes, two insulation tubes, a semi-conductive tube, protective tubes with adhesive, semi-conductive tape, lubricating grease, filling and sealing mastics, stress relief mastic, copper mesh, an earth wire, constant force springs and, in some versions, a conductor connector with shear bolts. The sheet says to make sure the system is de-energised and fully earthed before installation. The sheet's dimensions are examples of the level of detail, and they apply to that kit only:

StepExample from the sheet
Remove the oversheath1100 mm on one cable, with a 500 mm length for the anti-tracking tube
Remove the semi-conductive layer260 mm, with a bevelled cut at the edge
Strip the core insulation35 mm for 95 mm², 63 mm for 185 mm² and 70 mm for 300 mm²
Bevel the core insulation30 mm, leaving 5 mm of the inner semi-conductive layer
Clean the coreIn one direction only, from the insulation toward the semi-conductive screen, and never back and forth
Shrink the tubesFrom the centre toward the ends
Restore the earth and the oversheathCopper mesh, earth wire and constant force springs, then a protective tube that overlaps the oversheath by 100 mm on each side

The sheet gives no torch temperature or timing, so the jointer follows the kit's own heating instruction. Another kit, for another voltage or another maker, has other dimensions, which is the reason a jointer does not work from memory.

Terminations and cable types

A termination is made to suit the cable and the place. Single-core and three-core cables, copper wire screen and tape screen, armoured and unarmoured cable and XLPE and older paper-insulated lead-covered cable each have their own kit. An indoor termination suits a switchgear room. An outdoor termination has weather sheds to lengthen the surface path along the insulator, and it goes where rain and dust reach the cable end. Heat-shrink and cold-shrink technologies both exist at this voltage, and a transition joint connects an old paper cable to a newer XLPE one.

Who does the work

Medium-voltage jointing is done by trained jointers working to the kit maker's sheet. DEWA has a jointer certification page and an approved list of private cable laying contractors for 11 kV, 33 kV and low-voltage cable. The rules and the list change, so ask DEWA, or your consultant, what applies to your cable and your site.

We take 11 kV and 33 kV jointing, and we check the jointer's certification against DEWA's requirements before work starts. With any medium-voltage cable, do not open a cable end, do not open a ring main unit and do not allow anyone without a certificate to work on a live network.

What sets a kit price

A medium-voltage kit price is not a single number, because the kits differ in the ways below. A kit price from a catalogue is meaningless unless it names the following.

What changes the priceExamples
Voltage class11 kV and 33 kV kits are different products
Joint or terminationStraight joint, transition joint, branch or breech joint, indoor termination, outdoor termination
CoresSingle core or three core, and a set of three terminations for a three-phase circuit
Conductor size rangeEach kit covers a band of cross-sections, such as 25 to 630 mm² for one straight joint kit
InsulationXLPE or paper-insulated cable, which need different kits
ScreenCopper wire screen, copper tape or lead sheath
TechnologyHeat shrink or cold shrink
Connectors and extrasShear-bolt or crimp connectors, earthing parts and oversheath protection
MakerEach maker prices its own kit

The kit is one part of the cost. The jointer's time, the connectors where they are not in the kit, the earthing, the shutdown, the testing and the site safety make up the rest. We do not print a kit price here, because a price without the cable data, the size and the type would mislead. The site visit costs AED 50, and the quote follows it. If you have the cable data and need a figure, send the cable label and the photo of the cable end.

Cost

Cable termination and jointing cost: termination kit price, cable joint kit price and cable jointer price

The terms termination kit price, cable termination kit price and cable joint kit price each describe a part of the bill, and the price of a finished job is more than the price of the kit. A low-voltage kit is one line of the bill. The callout, the hydraulic tool and the hours of a skilled worker are others, and a good quote shows all of them.

What goes into the price of a termination

FactorWhy it changes the price
Number of terminationsEach core on each cable end is one lug, and a four-core cable has four lugs at each end
Cable sizeA 4 mm² core takes a hand tool and a 240 mm² core takes a hydraulic tool, a larger lug and more time
Armoured or unarmouredAn armoured cable needs a gland, with its earth tag and shroud
PlaceIndoor or outdoor, and a gland or an enclosure that is high, tight or hot
ShutdownWork on a board needs the supply off, and the shutdown may have to be arranged out of hours
TestsInsulation, continuity and phase checks, with a written record
MaterialThe lugs, glands, shrouds, boots and labels, bought at the size the cable needs

What goes into the price of a joint or a repair

FactorWhy it changes the price
Cable type and sizeThe kit is chosen for the cable, and a larger or multicore armoured cable needs a larger kit
TechnologyResin, heat shrink and cold shrink kits differ in cost and in time on site
AccessA joint in a trench, a riser or a ceiling void takes longer to reach and to make
Length of damageA short nick is a sheath repair, and a long crushed length is cut out and replaced
Digging and making goodA buried cable has to be located, exposed and covered again
TestsAn insulation test and an armour continuity check before and after

Cable jointer price

A cable jointer is a skilled person, and the price of one covers the skill, the tools, such as hydraulic crimpers and torches, the time and the risk. A jointer may quote per joint or per day, so ask which. Compare two quotes only when both say what is included: the kit, the connectors, the earthing, the test, the travel and the making good. A quote that gives a single figure with no list is not comparable to one that lists every item.

Cable jointing companies: how to choose

When you search for cable jointing companies, ask each one the same questions.

  1. 1
    Which kit will you use, and can I see the maker's sheet? A jointer who follows a sheet can show it.
  2. 2
    What evidence of competence can you show? Ask for the jointer's certificate or their record of past work for the voltage involved.
  3. 3
    What will you test, and will I get the figures? A joint without a test is a guess.
  4. 4
    Does the price include the armour bridge, the seal and the making good?
  5. 5
    Would a new length of cable be cheaper or sounder? An honest company says so when it is.
  6. 6
    Can I see photographs of earlier work?

Be careful of a price given without sight of the cable, a company that does not mention the armour or the earth, a joint wrapped in tape and a refusal to name the kit.

How we price

We give a fixed price after photos or a short visit, with parts, labour and tests on separate lines, so you can see what each part costs. If the right answer is a new cable and not a joint, we write that on the quote.

Testing and faults

Testing, labelling, handover and fixing termination and joint faults

A termination or a joint that looks right can still be wrong inside, so each one is tested and recorded before the cable is energised. The tests are short, and they are the only evidence that the work is sound.

The tests we run

  • Visual and mechanical check. Every crimp is tugged, no stray strand shows, every gland holds the cable against a pull, every bolt is torqued to the maker's table and marked with paint.
  • Continuity. Each core is checked end to end, and the armour or screen is checked for continuity across a joint and to the earth bar. We test core continuity before a joint is closed, because a closed joint cannot be reopened.
  • Insulation resistance. Each core is tested against the other cores and against earth. As an example from the UK wiring standard, a circuit up to 500 V is tested at 500 V DC and the reading must be at least 1 megohm. The cable maker's data and the standard you work to decide the figures. See our insulation and earth resistance testing page for the method.
  • Phase order. On a three-phase cable the phases must be the same at both ends. A joint that swaps two phases runs a motor backwards, so we check the order before the cable is energised.
  • Thermal check under load. Where the cable feeds a heavy load, a thermal image a few weeks after energising shows a hot lug or a hot joint before it fails.

Labelling and handover

We label each core at both ends and tag each cable with its circuit. We photograph the termination or the joint before it is closed, record the kit make and type, and write the test values and the date on the handover sheet. The joint's position goes on the drawing, so the next electrician can find it. You receive the photographs, the figures and the kit sheet.

Fixing termination and joint faults

SymptomLikely causeFix
A lug or a breaker is hot or discolouredA loose bolt, a lug that does not match the conductor, a poor crimp or an overloadIsolate, cut back to sound cable, fit the right lug, re-torque and check the load
A burning smell at a boardAn overheated termination or a loose connectionSwitch off, keep clear and call an electrician
A breaker trips after rainWater in a gland, a joint or a cable sheathReplace the BW gland with a sealed type, reseal the joint or repair the sheath, then test the insulation
Intermittent supply or a flickerA loose crimp or a half-made jointRemake the crimp or the joint
One phase is low or missingA bad lug, a loose connector or a cut coreTest each core and repair the break
A motor runs backward after a repairTwo phases were swappedRestore the correct phase order
Green or white deposit on a lugCorrosion from moisture or a mixed-metal contactCut back, clean, use the right lug and compound, and seal
A cable pulls out of a glandA gland that is the wrong size, or a clamp that was never tightenedRefit with the correct size and tighten as the sheet says
Noise on a control or data lineA screen not connected all the way roundRefit an EMC gland and test the screen to earth
Why us and how to book

Cable termination and jointing with Circuit Dubai

  • Electricians first, so the termination, the connection to the board or machine and the test are one job with one person responsible.
  • The right method for the cable, a crimp, a gland, a joint or a new length, chosen from the cable data and not from habit.
  • Every layer restored, meaning conductor, insulation, armour or screen and sheath.
  • Written test results, with the figures and the photographs at handover.
  • Plain advice on scope, including what we do not take on, such as medium-voltage work, where we say so.

We work across all of Dubai. Our office is in Al Quoz.

If you are also planning a DB box and distribution board upgrade, generator installation and servicing, pump and pool equipment wiring or an electrical inspection, we can plan the terminations for all of it together with the cable and gland work.

Our office: Office 1271, Oasis Mall, Al Quoz 1, Dubai, UAE
Phone: +971 55 407 7427
FAQs

Cable termination and jointing questions we hear from Dubai customers

How much does cable termination or jointing cost?

It depends on the number of terminations, the cable size, whether the cable is armoured, the place, the shutdown needed and the tests. A joint also depends on the cable type and the access. A site visit costs AED 50, and the price follows it. We give a fixed price after photos or a visit, with parts, labour and tests on separate lines.

What is a crimp connector and which size do I need?

A crimp connector is a metal barrel or lug that is squeezed onto a wire with a crimp tool. The size is set by the wire's cross-section, and the maker's chart gives the range for each connector. Red, blue and yellow insulated terminals are the colour-coded range, and the printed size on the terminal is the one to read.

What are yellow crimp connectors used for?

Yellow is the largest size in the red, blue and yellow range of pre-insulated terminals, and maker charts pair it with wire of about 4 to 6 mm². Bootlace ferrule colours follow a different code, so a yellow ferrule is not the same as a yellow terminal.

Can I use wire to wire crimp connectors in a junction box?

Yes, a correctly crimped butt connector or parallel connector inside a box that can be opened is an accessible joint. The wire size, the connector and the die have to match, and a crimp inside a wall with no box is a hidden joint, which we do not make.

Can I crimp with ordinary pliers?

We do not. A ratchet crimp tool with the right die closes the barrel evenly and cannot be opened until the crimp is complete. A plier can flatten one side of the barrel and leave the strands loose inside it.

Do I need a BW or a CW gland?

A BW gland grips the armour and does not seal the outer sheath, so it suits a dry indoor termination. A CW gland also seals the outer sheath, so it suits an outdoor, wet or dusty place. A BW gland on an outdoor cable lets water into the board.

Do you supply Connectwell cable glands?

Connectwell is a make of cable gland, and we fit the make the job specifies or an equal of the same type and rating. We do not claim to be an authorised dealer of any make.

What is an EMC cable gland and do I need one?

An EMC gland clamps the metal screen of a cable all the way round to the enclosure. It is needed on a screened cable where noise is a risk, such as a motor cable from a variable-speed drive. A cable without a screen needs a standard gland.

How do you fit an armoured cable gland?

We strip the outer sheath to the length on the gland's sheet, fit the shroud, fit the gland into the enclosure with its locknut and earth tag, spread the armour evenly around the cone, tighten the nut until the armour is held, tighten the seal on a CW gland, connect the earth tag and test the grip. The sheet of the gland in the box gives the dimensions.

Can a damaged power cable be repaired?

Yes, where the damage can be repaired. A nick in the sheath needs a sheath repair. Damage to the insulation or conductor needs a straight joint or a new length. A crushed or burnt cable is cut back to sound cable. We tell you which fits after we see the damage and the cable.

Can you make a cable joint inside a wall or ceiling?

We try to avoid one. A connection in a wall cannot be inspected, so where we can we use one length or place the joint in a box that opens. Where a joint cannot be avoided, we mark its position on the drawing.

Can you repair an EV charging cable?

We do not splice a damaged charging cable. A charging cable is a made assembly, and a damaged one is replaced or returned to the maker. We repair the fixed wiring around the charger, such as the supply cable, the gland and the termination.

Do you do 11kV and 33kV cable jointing?

Yes. We take 11 kV and 33 kV jointing, and we check the jointer's certification against DEWA's requirements before work starts. Medium-voltage work on the DEWA network is subject to DEWA's own requirements.

What tests do you do after a termination or joint?

We tug every crimp, check each gland, mark the torque, check continuity of each core and the armour, test the insulation between cores and to earth, and check the phase order on three-phase cable. You receive the figures.

Can aluminium cable be joined to copper?

Only with parts made for it. An aluminium conductor needs an aluminium lug, or a bimetallic lug against a copper busbar, and the maker's instruction on oxide-inhibiting compound has to be followed. A copper lug not made for aluminium corrodes at the contact.

Is there someone near me who can repair a cable today?

Our office is at Office 1271, Oasis Mall, Al Quoz 1, Dubai, and we work across Dubai. Send photos of the damage and the cable printing on WhatsApp and tell us if the supply is off. We answer emergency messages 24 hours a day, 7 days a week, and a technician can be on site within 30 minutes anywhere in Dubai.

Do speaker wires need crimp connectors?

They do not need them, but a spade or pin connector on speaker wire stops stray strands from touching the next terminal. Match the connector to the wire gauge and keep the polarity the same at both ends.

Ready to book cable termination, jointing or cable repair?

Send photos of the cable and the damage, the printing on the cable sheath, the number of cores and the size if you know it, and say what it connects to and whether it is indoors, outdoors or underground. Tell us if the supply is switched off. We reply instantly on chat with a view on whether a termination, a joint or a new length is right, and a fixed price, so you know what you are buying before anyone cuts a cable.